| Compaq ProLiant
BL p-Class Server Blade Enclosure |
Dimensions |
Height |
10.5 in/26.67 cm |
|
Width |
17.60 in/44.70 cm |
|
Depth |
28.86 in/73.30 cm |
|
Input
Specifications |
Rated input voltage |
-43 VDC to -53 VDC |
Nominal -48 VDC |
|
Rated input current |
62.5 A at -48 VDC |
|
Rated
input Power |
3000 W |
|
Individual server blade bay ratings |
Rated
input voltage |
-43 VDC
to -53 VDC |
Nominal -48 VDC |
|
Rated input current |
6.25 A at -48 VDC |
|
|
Rated input Power |
300 W |
|
Temperature range |
Operating |
50° to 95° F/10°
to 35° C |
|
|
Non-Operating |
-22° to 140°
F/-30° to 60° C |
|
Relative
humidity
(non-condensing) |
Operating |
20% to 80% |
|
Non-Operating |
5% to 95% |
|
Wet bulb
temperature |
Operating |
82.4° F/28° C |
|
|
Non-Operating |
101.7° F/38.7° C |
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
|
| Operating and
Performance Specifications for ProLiant BL20p Server Blade |
Dimensions |
Height |
1.69 in/4.29 cm |
|
Width |
10.29 in/26.14 cm |
|
Depth |
28.00 in/71.12 cm |
|
Weight (maximum) |
18.0 lb/8.17 kg |
|
|
Temperature range |
Operating |
50° to 95° F/10°
to 35° C |
|
|
Non-operating |
|
|
|
|
Shipping |
-40° to 140°
F/-40° to 60° C |
|
|
|
Storage |
-4° to 140° F/-20°
to 60° C |
|
Relative
humidity
(non-condensing) |
Operating |
10% to 90% |
|
Non-operating |
|
|
|
|
Shipping |
10% to 90% |
|
|
|
Storage |
10% to 95% |
|
Maximum
wet bulb temperature |
82°
F/28° C |
|
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
| Operating and
Performance Specifications for RJ-45 Patch Panel |
Dimensions |
Height |
10.405 in/26.43 cm |
|
Width |
1.535 in/3.899 cm |
|
Depth |
27.697 in/70.35 cm |
|
Capability |
IEEE 802.2, 802.3,
802.3u |
|
|
Network transfer
rate |
10 Base-T
(half-duplex) |
10 Mbps |
|
|
10 Base-T
(full-duplex) |
20 Mbps |
|
|
100 Base-TX
(half-duplex) |
100 Mbps |
|
|
100 Base-TX
(full-duplex) |
200 Mbps |
|
|
1000 Base-TX
(full-duplex) |
1000 Mbps |
|
Connector |
RJ-45 |
|
|
Cable support |
10 Base-TX |
Categories 3, 4, or 5
UTP (2 or 4 pair); up to 328 ft/100 m |
|
|
100 Base-TX |
Category 5 UTP (2
pair); up to 328 ft/100 m |
|
|
1000 Base-TX |
Category 5E (4 pair);
up to 328 ft/100 m |
|
Power requirements |
200 mA at + 5V DC; 500 mA at -48V |
|
Temperature range |
Operating |
50° to 95° F/10°
to 35° C |
|
|
Non-operating |
-22° to 140°
F/-30° to 60° C |
|
Relative
humidity (non-condensing) |
Operating |
20% to 80% |
|
Non-operating |
5% to 95% |
|
Wet
bulb temperature |
Operating |
82.4° F/28° C |
|
Non-operating |
101.7° F/38.7° C |
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
| Operating and
Performance Specifications for Interconnect GbE Switch |
Dimensions |
Height |
10.405 in/26.43 cm |
|
Width |
1.535 in/3.899 cm |
|
Depth |
27.697 in/70.35 cm |
|
Weight |
11.5 lb/5.2 kg per
interconnect switch |
|
Performance |
3.2 Gbps Switching
bandwidth per server enclosure |
|
|
4.4 Gbps uplink
bandwidth per server enclosure |
|
|
9.6 Million pps
aggregate throughput per server enclosure (64-byte packets) |
|
|
Full-wire speed for
all connections |
|
|
Auto-negotiation and
auto-sensing with full-duplex support |
|
Forwarding mode |
Store and forward |
|
MAC Addresses |
8,191 per
interconnect switch; MAC address based filtering and MAC address packet priority
configuring |
|
Forwarding table
age time |
Maximum age: 10 to
9999 seconds; default: 3000 seconds |
|
Memory |
32MB Main, 6MB flash
and 16MB packet buffer per interconnect switch |
|
Compliance |
IEEE 802.3, 802.3u,
802.3ab, 802.3z, 802.1D, 802.1p, 802.3ac, 802.3ad (Static), 802.1Q, and 802.3x |
|
|
SNMP v1 (RFC 1157)
and RMON v1 (RFC 1757) groups 1, 2, 3, and 9 |
|
|
MIB-II (RFC 1213),
Bridge MIB (RFC 1493), Interface MIB (RFC 2233), 801.1Q MIB (RFC 2684), RMON1 MIB (RFC
1757) groups 1, 2, 3, and 9, and Ethernet MIB (RFC1643) |
|
Network transfer
rate |
10 Base-T
(half-duplex) |
10 Mbps |
|
|
10 Base-T
(full-duplex) |
20 Mbps |
|
|
100 Base-TX
(half-duplex) |
100 Mbps |
|
|
100 Base-TX
(full-duplex) |
200 Mbps |
|
|
1000 Base-TX
(half-duplex) |
1000 Mbps |
|
|
1000 Base-TX
(full-duplex) |
2000 Mbps |
|
|
1000 Base-SX
(full-duplex) |
2000 Mbps |
|
Connector |
RJ-45, DB-9 (C-GbE
Interconnect Kit)
LC fiber, RJ-45, DB-9 (F-GbE Interconnect Kit) |
|
EMI |
FCC Class A |
|
|
ICES-003 Class A |
|
|
AS/NZS 3548 Class A |
|
|
VCCI Class A |
|
Safety |
UL/CUL Listed
Accessory |
|
Power requirements |
48V: 1050 mA, 50 W
maximum (per interconnect switch) |
|
Temperature range |
Operating |
50° to 95° F/10°
to 35° C |
|
|
Non-operating |
-22° to 140°
F/-30° to 60° C |
|
Relative
humidity
(non-condensing) |
Operating |
20% to 80% |
|
Non-operating |
5% to 95% |
|
Wet
bulb temperature |
Operating |
82.4° F/28° C |
|
Non-operating |
101.7° F/38.7° C |
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
| Operating and
Performance Specifications for Power Enclosures (North America/Japan) |
|
|
Single-Phase Model |
Three-Phase Model |
| Dimensions |
Height |
5.25 in/13.34 cm |
5.25 in/13.34 cm |
|
Width |
17.60 in/44.7 cm |
17.60 in/44.7 cm |
|
Depth |
27.15 in/68.96 cm |
27.15 in/68.96 cm |
|
Weights |
No hot-plug power
supplies |
47.5 lb/21.55 kg |
47.5 lb/21.55 kg |
|
All hot-plug power
supplies |
99.5 lb/45.13 kg |
125.5 lb/56.93 kg |
|
Input
requirements |
Rated
input voltage |
200 VAC
to 240 VAC |
200 VAC
to 240 VAC line to line |
|
Rated input frequency |
50 Hz to 60 Hz |
50 Hz to 60 Hz |
|
Rated input current
per side |
24A |
24A per phase |
|
Rated input power per
side |
5760 W |
9976 W |
|
Power cord |
1 NEMA L6-30P per
side |
1 NEMA L15-30 per
side |
|
Output
voltage specifications |
Rated output voltage |
-48.8 VDC to -54 VDC |
-48.8 VDC to -54 VDC |
| Rated output current |
99A |
170A |
|
Rated output power |
4298 W |
8310 W |
|
Nominal power |
4158 W at 208 VAC |
7202 W at 208 VAC |
|
Ambient
temperature range (See NOTE) |
Operating |
50° to 95° F/10°
to 35° C |
50° to 95° F/10°
to 35° C |
| Shipping |
-22° to 140°F/-30°
to 60°C |
-22° to 140°F/-30°
to 60°C |
|
Relative
humidity,
non-condensing
(See NOTE) |
Operating |
20% to 80% |
20% to 80% |
| Non-operating |
5% to 95% |
5% to 95% |
|
Wet
bulb temperature |
Operating |
82.4° F/28° C |
82.4° F/28° C |
| Non-operating |
101.7° F/38.7° C |
101.7° F/38.7° C |
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
| Operating and
Performance Specifications for Power Enclosures (International) |
|
|
Single-Phase Model |
Three-Phase Model |
| Dimensions |
Height |
5.25 in/13.34 cm |
5.25 in/13.34 cm |
|
Width |
17.60 in/44.7 cm |
17.60 in/44.7 cm |
|
Depth |
27.15 in/68.96 cm |
27.15 in/68.96 cm |
|
Weights |
No hot-plug power
supplies |
47.5 lb/21.55 kg |
47.5 lb/21.55 kg |
|
All hot-plug power
supplies |
99.5 lb/45.13 kg |
125.5 lb/56.93 kg |
|
Input requirements |
Rated input voltage |
200 VAC to 240 VAC |
6.25 A at -48 VDC 200
VAC to 240 VAC line to neutral |
|
Rated input frequency |
50 Hz to 60 Hz |
50 Hz to 60 Hz |
|
Rated input current
per side |
24A |
20A per phase |
|
Rated input power per
side |
5760 W |
10,552 W |
|
Power cord |
1 IEC 309 3-pin, 32A
per side |
1 IEC 309 5-pin, 32A
per side |
|
Output
voltage specifications |
Rated output voltage |
-48.8 VDC to -54 VDC |
-48.8 VDC to -54 VDC |
| Rated output current |
99A |
180A |
|
Rated output power |
4798 W |
8790 W |
|
Nominal power |
4598 W at 208 VAC |
8790 W at 230 VAC L-N |
|
Ambient
temperature range (See NOTE) |
Operating |
50° to 95° F/10°
to 35° C |
50° to 95° F/10°
to 35° C |
| Shipping |
-22° to 140°F/-30°
to 60°C |
-22° to 140°F/-30°
to 60°C |
|
Relative
humidity,
non-condensing
(See NOTE) |
Operating |
20% to 80% |
20% to 80% |
| Non-operating |
5% to 95% |
5% to 95% |
|
Wet
bulb temperature |
Operating |
82.4° F/28° C |
82.4° F/28° C |
| Non-operating |
101.7° F/38.7° C |
101.7° F/38.7° C |
|
NOTE:
Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No
direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper
non-operating limit is 30,000 ft/9,144 m or 30.3 KPa/4.4 psia. Storage maximum
humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa. |
| |
| Operating and
Performance Specifications for Power Distribution Devices |
|
Power Bus Box |
Mini Bus Bar |
Scalable Bus Bar |
Power enclosures
or facility DC feeds supported
(3U each) |
1 |
1 |
2 |
| Server blade
enclosures supported (6U each) |
1 |
3 |
5 |
|
Total rack height
of supported enclosures |
9U |
21U |
36U |
|
Dimensions |
|
|
|
|
|
Height |
5.1
in/12.95 cm |
19.45
in/49.40 cm |
48.57
in/123.37 cm |
|
|
Width |
3.6
in/9.14 cm each |
19.74
in/50.14 cm |
19.74
in/50.14 cm |
|
|
Depth |
3.25
in/8.26 cm |
2.2
in/5.59 cm |
2.2
in/5.59 cm |
|
Weight |
3.62
lb/1.64 kg |
13.2
lb/59.9 kg |
26
lb/11.79 kg |
|
Rated
operating voltage |
-43.2 VDC
to -54 VDC |
-43.2 VDC
to -54 VDC |
-43.2 VDC
to -54 VDC |
|
Max
total power supported |
3000 W |
9000 W |
15,000 W |
|
Total
max input current at minimum voltage |
69.44 A at
-43.2VDC |
208.32 A
at -43.2 VDC |
347.2 A at
-43.2 VDC
(equivalent of 175A per feed) |
|
Total
max input current at nominal voltage |
62.5 A at
-48VDC |
187.5 A at
-48 VDC |
312.5 A at
-48 VDC
(equivalent of 175A per feed) |
|
Max
current per power feed |
70A |
210A |
210A |
|
Max
local ambient temperature |
149°
F/65° C |
149°
F/65° C |
149°
F/65° C |
|
NOTE: All systems support redundant A & B feeds. Scalable bus
bar supports dual A and dual B feeds. |
| |
| Operating and
Performance Specifications for Facility DC |
Voltage |
Nominal input voltage |
-48 VDC |
|
Operating voltage
range |
-48VDC ± 10% or -43.2 VDC to -52.8 VDC |
|
|
Max Input voltage
slew rate |
0.5V/uS |
|
|
Redundant feed
voltages*
(A & B) |
*A and B feeds must differ by no more than 5VDC during steady state
operation |
|
|
Ripple/Noise |
480 mV PARD** |
|
|
Overshoot |
Must remain within
regulation limits on all feeds during startup or shutdown |
|
|
Voltage transients |
Must not exceed -60
VDC |
|
Current |
Max steady state
input current |
62.5A per server
blade enclosure installed at -48VDC |
|
|
Max steady state
current per feed/total |
|
|
|
|
Power bus boxes |
70 A/70A |
|
|
|
Mini bus bars |
210 A/210A |
|
|
|
Scalable bus bars |
210 A/350A or
equivalent of 175A per feed* |
|
In-rush
current |
Must
support up to 2X the maximum operating current per server blade enclosure (125 A) for up
to 1.0 mS |
|
Input
over-current |
Customer
provided fusing for facility DC feeds that protects the system from catastrophic
over-current within 20 uS. Fuse should sustain all in-rush and operating currents. |
|
Max
Input Current Slew Rate |
1A/uS |
|
Max
Rated Power |
3000W
per server blade enclosure |
| Connections
and Cables |
HP
provided facility DC cable connection kit:
- The facility DC connection kit supports the connection of up to four -48VDC, RETURN
pairs and ground.
The power cable assemblies consist of 1/0AWG, color-coded, flexible cable rated at
105° C, terminated with bus mating connectors at one end and unterminated at the other
end. The cable length provided enables the customer to route to a fuse panel within or
adjacent to the rack. |
|
NOTE: *All systems support redundant A and B feeds. Scalable bus
bars support dual A and dual B feeds.
** Periodic and random noise (PARD). Maximum allowable peak-to-peak ripple and noise (as
measured at the load on any output channel). The ripple and noise is measured over a 20 Hz
to 100 MHz frequency band. A resistive load (non-electronic) is used for this measurement.
Each output is by-passed to return by a 10uF tantalum capacitor with an ESR less than 100
milli-Ohms in parallel with a 0.47 uF ceramic capacitor, at the point of load. The load
cable is 12 feet of twisted wire capable of carrying the current. The printed wiring board
assembly is installed in its enclosure for this measurement, or the measurement leads are
properly shielded with Earth grounds applied to the insert. |